Parallel Pumping in Condenser Applications: Part 2 of 5

Parallel Pumping in Condenser Applications: Part 2 of 5

In Part 1 of this series we offered an example of a condenser water pumping system with 800 GPM per condenser for a total of 1600 GPM with the third condenser serving as standby. The tower elevation or lift is 10 feet, the condenser (with the 2-way valve and balance valve) has 20 feet of pressure drop, and the common piping with any safety factor has 30 feet of pressure drop. But there was a problem....

Read More

Parallel Pumping in Condenser Applications: Part 1 of 5

Parallel Pumping in Condenser Applications: Part 1 of 5

Applying a single constant speed pump for each condenser in a chilled water application is a normal design for the HVAC engineer. Some chiller manufacturers suggest piping the pumps with a common header and activating each pump as the condensers are staged on. However, there is a hidden issue with this approach, which, if not addressed may cause major problems....

Read More

Cooling Tower and Condenser Water Design Part 6: Multiple Cooling Towers and Condenser Piping

Larger facilities often have multiple cooling towers serving multiple chillers, enabling them to more closely match demand. Piping such systems can be a challenge, depending on the amount of flexibility desired. Here we describe the three most common approaches to piping multiple cooling towers and chillers.
Read More

Understanding Primary Secondary Pumping Part 5: Best Practices for Piping

By Chris Edmondson

Piping in a primary secondary pumping systems as a whole can be quite complex, but when it comes to the “primary” part of the system, there are really only two approaches:  Dedicated or Non-dedicated.

Figure 1 shows the chillers in a primary secondary system piped with one pump per chiller.  If the chillers

Read More